GPR-2500 IS % O2 TRANSMITTER
Xuất sứ: USA
Nhà cung cấp: ANS Vietnam
Hãng sản xuất: Aii1
Ứng dụng sản phẩm: Natural Gas Products
Liên hệ tư vấn
Intrinsically safe % oxygen transmitter with integral safety barrier, ATEX, cUL, and CSA certified 2-wire loop powered 4-20 mA transmitter measures O2 concentrations from 0- 25% with 0-1% full scale low range. Designed exclusively for Natural Gas applications. This transmitter features an advanced galvanic oxygen sensor, a 36 month operating life, and menu driven controls.
Certifications:
cUL Class I Div I Group C, D
ATEX Directive 94/9/ EC
Ex d [ib] ib IIB T4 Gb
Tamb -10oC to 50oC
*Accuracy: | < 2% of FS range under constant conditions | Analysis: |
0-1%, 0-5%, 0-10%, 0-25% FS ranges; |
Application: | Oxygen analysis in inert, hydrocarbon, hydrogen, mixed and acid (CO2) gas streams | Approvals: | Ex d [ib] ib IIB GbT4 Tamb -20⁰C to +50⁰C |
Area Classification: | cUL approved for use in Class 1, Division 1, Group C, D hazardous areas | Alarms: | NA |
Calibration: | Air or certified span gas | Compensation: | Barometric pressure and temperature |
Connections: | 1/8″ compression tube fittings | Controls: | Water resistant keypad; menu driven range selection, calibration and system functions |
Display: | Graphical LCD 2.75” x 1.375”; resolution 0.001% | Enclosure: | Aluminum ex-proof, fiberglass NEMA 4X, 16x9x6”, 20 lbs |
Flow Sensitivity: | None between 0.5-5 SCFH, 1-2 SCFH recommended | Linearity: | ±2% of full scale |
Pressure: | Inlet – regulate to 5-30 psig; vent – atmospheric | Power: | 18-24 VDC (suitable for solar powered systems) |
Response Time: | 90% of final reading in 10 seconds | Sample System: | Sample flow meter |
Sensitivity: | < 0.5% of FS range | Sensor Model: | XLT-11-24 for gases containing > 0.5% CO2 |
Sensor Life: | 24 months at 25ºC and 1 atm. | Signal Output: | 4-20mA Loop Current |
Operating Range: | Recommended -10ºto 45ºC | Warranty: | 12 months analyzer; 12 months sensor |
Wetted Parts: | Stainless steel |
*At constant temperature and pressure
Optional Equipment | |||
GPR-11-32 | Sensor for measuring oxygen in inert gases | ||
Sample System | Pressure regulator, sample/span valve | ||
Enclosure | Analyzer housed in NEMA 4 Enclosure |